Welcome to visit   Zhongkuang Runze Technology (Xuzhou) Co., Ltd 简体中文   |   ENGLISH
Mining explosion-proof and intrinsically safe leakage line selection device
ZJL10(6) / 48


Application Scope

Central high-voltage substations in underground coal mines, 6kV/10kV high-voltage power distribution chambers in mining areas, underground main drainage, main ventilation, main hoisting high-voltage power supply systems, surface coal preparation plants, high-voltage low-current grounding systems in gas drainage stations, and underground high-voltage power distribution systems in other metal and non-metal mines.

Parameter Information

Equipment Model Working Voltage Applicable Voltage Number of Monitoring Lines
ZJL10/48 Two-channel AC127V 10KV Power Grid 4 bus sections/12 branches each
ZJL6/48 Two-channel AC127V 6KV Power Grid 4 bus sections/12 branches each

Main Performance

1. Product specifications: Dimensions: (Length×Width×Height) 650mm×608mm×1306mm. Weight: approximately 290kg.

2. The product has a dual power supply system, with main and backup power supplies interlocked, ensuring that only one power supply is connected at any time.

3. Fault line selection function: When a single-phase grounding fault occurs in the system, the device can accurately determine the faulty line and display the on-site number of the faulty line.

4. Storage and memory function: The device can save 200 pieces of leakage grounding fault information. The fault information includes the fault occurrence time and on-site branch number. After the device loses power, the fault record data will not be lost.

5. Communication function: Equipped with an intrinsically safe network communication interface, providing data upload.

6. Setting value modification function: The device parameters and setting values can be set locally, such as the alarm limits of zero-sequence voltage and zero-sequence current, and line names.

7. Ultra-large protection capacity: Four bus sections and 48 outgoing lines with real-time online insulation monitoring, and advance pre-alarm for insulation degradation.

8. Two protection modes optional: Alarm only / Alarm + branch selective tripping.


Applicable Places

1. Power supply trunk lines for underground coal mine mining and excavation working faces
The power supply lines for mining and excavation working faces have many branches and mixed loads, and are areas with a high incidence of leakage faults, with a high risk level of gas and coal dust explosions. When a single-phase leakage or grounding fault occurs, the device can accurately locate the faulty branch and quickly cut off the leakage circuit, avoiding electric sparks generated by leakage current igniting gas and coal dust; at the same time, it does not interrupt the power supply of intact branches, ensuring the continuous operation of mining and excavation equipment, gas monitoring, and spray dust reduction systems on the working face, and eliminating blind spots in leakage monitoring.

2. High-voltage and low-voltage power supply systems of underground central substations and mining area substations
Underground main substations and mining area substations are the power supply hubs of the entire mine, with multiple parallel cables laid. Traditional leakage protection can only trip the entire system, and fault troubleshooting takes a long time. This device can achieve accurate line selection for multi-circuit leakage faults and quickly distinguish faulty outgoing branches, cutting off only the faulty line while other power supply circuits continue to operate without interruption. This takes into account the power supply continuity of underground relay protection, operating power, and lighting systems, and meets the safety specifications for underground explosion-proof electrical equipment.

3. Power supply circuits of key lifeline equipment such as underground main ventilation, drainage, and compressed air
Main fans, drainage pumps, and air compressors are core mine safety lifeline equipment. Their supporting power supply cables are laid over long distances and are prone to damage and leakage in humid environments. The device monitors the leakage parameters of each branch in real time. Once leakage grounding occurs, it accurately locks the faulty cable and selectively trips to isolate the fault, preventing leakage from causing interruption of ventilation or drainage, and avoiding major safety accidents such as gas accumulation and tunnel flooding.

4. Underground belt conveyor and rail transportation automated power supply networks
The branch lines of underground belt conveyors, winches, transfer machines, and other transportation systems are densely distributed. Tunnel water spraying and mechanical dragging can easily cause cable insulation damage and leakage. Ordinary leakage protection with full-line power outage will cause the entire transportation system to stop, which can easily lead to coal stacking and runaway car hazards. The leakage line selection device accurately identifies the faulty branch and cuts off only the faulty line, while intact transportation equipment continues to operate, ensuring continuous and stable underground material transportation.

5. Power supply branch circuits of underground electromechanical chambers and mobile substations
Underground mobile substations and hydraulic support electro-hydraulic control chambers have narrow spaces and dense equipment, and cables are frequently bent and worn, resulting in prominent leakage risks. The device is suitable for explosion-proof power supply systems, quickly performs line selection and tripping, narrows the scope of fault power outage, protects the stable power supply of electro-hydraulic control and monitoring communication equipment, and meets the safety control requirements of underground high explosion-proof and high intrinsically safe electrical places.


Return